Document IIF

Analyse énergétique et exergétique d’un système à absorption fonctionnant avec des couples de travail LiBr-H2O et Carrol-H2O pour des applications de refroidissement et de chauffage.

Energy and exergy analysis of an absorption system with working pairs LiBr-H2O and Carrol-H2O at applications of cooling and heating.

Auteurs : ZHENG J., CASTRO J., OLIVA A., OLIET C.

Type d'article : Article de la RIF

Résumé

In this work, an air-cooled, single effect solar-driven absorption system is being evaluated from the point of view of 1 and 2 thermodynamic principles for two different applications: absorption chiller and heat pump. One of the most widely used working pairs, LiBr-HO, is applied in this study due to its high performance in the absorption cycle. Their performance is compared with another working pair Carrol-HO (Carrol contains LiBr and EG -Ethylene glycol- with a mass ratio of 4.5:1). The Carrol solution has the advantage of reducing the crystallization risk at the high concentration solution that enters the absorber. The numerical modelling was implemented on a modular object-oriented simulation platform (NEST platform tool), which allows linking different components, considered objects. In the simulations performed, the heat source temperature in the system is in the range of 70–90 C, and the inlet temperature at evaporator secondary circuit at chiller application is fixed in two values, 9C and 14C, and for heat pump application in 0C and -5C. Moreover, EG is added to the evaporator at heat pump application to prevent the refrigerant water from freezing below zero. The studied mass concentration range of EG of 10–40%. The result shows the of an absorption chiller and heat pump are around 0.7 and 1.6, respectively, and the values are 0.2-0.6 at chiller application and 0.5-1.5 at heat pump application. When compared with LiBr system, Carrol system has about 6.4% higher , about 6.3% higher , and a decrease of about 19% of cooling capacity. In the heat pump application, the heat source temperature should be lower than 90C, and EG concentration at evaporator has been chosen as 30% as an optimal value. According to the operation condition, this EG concentration has been determined to avoid freezing in the evaporator in the studied working range. However, too much EG significantly decreases the pressure in the evaporator and increases the viscosity, hence will increase the maintenance of equipment as more vacuum tightness is required.

Documents disponibles

Format PDF

Pages : 156-171

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Energy and exergy analysis of an absorption system with working pairs LiBr-H2O and Carrol-H2O at applications of cooling and heating.
  • Identifiant de la fiche : 30029222
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 132
  • Date d'édition : 12/2021
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2021.09.011
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.