Analyse expérimentale comparative étalée sur trois ans d'un système de conditionnement d'air à base de déshydratant installé dans une serre à fleurs : évaluation de plusieurs déshydratants.
Three years experimental comparative analysis of a desiccant based air conditioning system for a flower greenhouse: Assessment of different desiccants.
Auteurs : LONGO G. A., GASPARELLA A.
Type d'article : Article
Résumé
This paper presents three years experimental comparative analysis of a desiccant-based and a traditional air conditioning system for a flower greenhouse in the winter season. Two identical neighbouring flower greenhouses were equipped with a traditional and an innovative air conditioning system respectively. The innovative air conditioning system is based on the Ventilated Latent Heat Converter (VLHC) AGAM 1020 that consists of a dehumidification and a regeneration unit. Heat recovery is performed on the desiccant regeneration process to warm up the dehumidified air coming back into the greenhouse.
Comparative analysis was carried out for three years using three different desiccants in the VLHC: H2O/LiCl in 2010, H2O/KCOOH in 2011 and H2O/LiBr in 2012. The greenhouse equipped with a sorption unit exhibits an energy saving of 9.6% in 2010, 11.7% in 2011, and 15.1% energy saving in 2012. The comparative analysis gives the opportunity for the assessment of the hygroscopic salt solutions currently used as desiccants. Although H2O/LiBr desiccant exhibits the best performance, the solution H2O/KCOOH seems to be very promising as “desiccant of the future”.
Détails
- Titre original : Three years experimental comparative analysis of a desiccant based air conditioning system for a flower greenhouse: Assessment of different desiccants.
- Identifiant de la fiche : 30014873
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 78
- Date d'édition : 03/2015
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2014.12.005
Liens
Voir d'autres articles du même numéro (19)
Voir la source
-
Three years experimental comparative analysis o...
- Auteurs : LONGO G. A., GASPARELLA A.
- Date : 02/03/2014
- Langues : Anglais
- Source : International sorption heat pump conference (ISHPC2014), College Park, United States, March 31-April 2, 2014.
- Formats : PDF
Voir la fiche
-
Le refroidissement par déshydratant au banc d'e...
- Auteurs : SCHILLER H.
- Date : 11/11/1996
- Langues : Allemand
- Source : CCI Zeitung - vol. 30 - n. 13
Voir la fiche
-
Analytical solution of combined heat and mass t...
- Auteurs : LIU X. H., JIANG Y., QU K. Y.
- Date : 08/2008
- Langues : Anglais
- Source : International Journal of Heat and Mass Transfer - vol. 51 - n. 17-18
Voir la fiche
-
Experimental analysis of a desiccant-based air-...
- Auteurs : LONGO G. A., GASPARELLA A., STORATO S.
- Date : 06/04/2011
- Langues : Anglais
- Source : Sources/sinks Alternative to the Outside Air for Heat Pump and Air-conditioning Techniques (Alternative Sources - AS), Padua, Italy, April 5-7, 2011. / International Sorption Heat Pump Conference (ISHPC11), Padua, Italy, April 6-8, 2011.
- Formats : PDF
Voir la fiche
-
Performance comparison of waste heat-driven des...
- Auteurs : COWIE M., LIAO X., RADERMACHER R.
- Date : 2003
- Langues : Anglais
- Source : ASHRAE Transactions. 2003 annual Meeting, Kansas City, Missouri, USA. Volume 109, part 2 + CD-ROM.
Voir la fiche