Document IIF
Analyse paramétrique sur l’effet des variables de conception et de fonctionnement dans un désorbeur à membrane.
A parametric analysis on the effect of design and operating variables in a membrane-based desorber.
Auteurs : VENEGAS M., GARCIA-HERNANDO N., VEGA M. de
Type d'article : Article, Article de la RIF
Résumé
A parametric analysis of a membrane-based microchannel desorber working with H2O–LiBr is presented. Mass and heat transfer equations are solved, for different membrane properties and design and operating conditions. Sensitivity of the ratio between chiller cooling capacity and desorber volume (rqV) to changes in the following parameters is evaluated: width and height of solution and hot water channels; solution concentration, temperature, pressure and mass flow rate; hot water temperature and mass flow rate; membrane porosity, pore diameter and thickness; thickness and thermal conductivity of the wall between solution and hot water and vapour pressure. The analysis includes direct diffusion and boiling modes. In both cases, during design, most important parameters to maximize rqV are solution channel height and wall thickness. Additionally, effect of channel length is remarkable during boiling. Good operation requires adequate inlet concentration and hot water temperature. In direct diffusion, vapour pressure is also a relevant parameter.
Documents disponibles
Format PDF
Pages : 47-58
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : A parametric analysis on the effect of design and operating variables in a membrane-based desorber.
- Identifiant de la fiche : 30025486
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 99
- Date d'édition : 03/2019
- DOI : http://dx.doi.org/10.1016/j.ijrefrig.2018.11.043
Liens
Voir d'autres articles du même numéro (45)
Voir la source
Indexation
-
Optimal control of single stage LiBr/water abso...
- Auteurs : SABBAGH A. A., GOMEZ J. M.
- Date : 08/2018
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 92
- Formats : PDF
Voir la fiche
-
Alternative designs for a 24-hours operating so...
- Auteurs : AL-UGLA A. A, SHAARAWI M. A. el-, SAID S. A. M.
- Date : 05/2015
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 53
- Formats : PDF
Voir la fiche
-
Climatizzazione invernale con deumidificazione ...
- Auteurs : D'ASCANIO A., LAZZARIN R.
- Date : 11/2003
- Langues : Italien
- Source : Cond. Aria - n. 10
Voir la fiche
-
Climatizzazione estiva con deumidificazione chi...
- Auteurs : D'ASCANIO A., LAZZARIN R.
- Date : 12/2003
- Langues : Italien
- Source : Cond. Aria - n. 11
Voir la fiche
-
Optimal temperature of collector for solar doub...
- Auteurs : LI Z., YE X., LIU J.
- Date : 08/2014
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 69 - n. 1-2
Voir la fiche