Analyse thermodynamique d'un cycle frigorifique transcritique au CO2 avec éjecteur.

Thermodynamic analysis of transcritical CO2 refrigeration cycle with an ejector.

Auteurs : SUN F., MA Y. T.

Type d'article : Article

Résumé

A comparative study on transcritical carbon dioxide refrigeration cycle with ejector and with throttling valve was performed by the first and second laws of thermodynamics in theory. The effects of the entrainment ratio of the ejector, heat rejection pressure, outlet temperature of gas cooler and evaporating temperature on the coefficient of performance (COP) and exergy loss were investigated in transcritical carbon dioxide refrigeration cycle with ejector and with throttling valve. It is found that ejector instead of throttling valve can reduce more 25% exergy loss and increase COP more 30%. In addition, critical entrainment ratio of the ejector, optimal heat rejection pressure and critical outlet temperature of gas cooler affects COP greatly for the transcritical carbon dioxide refrigerating cycle with ejector. [Reprinted with permission of Elsevier. Copyright 2011.]

Détails

  • Titre original : Thermodynamic analysis of transcritical CO2 refrigeration cycle with an ejector.
  • Identifiant de la fiche : 30003687
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 31 - n.6-7
  • Date d'édition : 05/2011
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2010.12.018

Liens


Voir d'autres articles du même numéro (11)
Voir la source