Analyse thermoéconomique d'un système de conditionnement d'air évaporatif à déshydratant.

Thermoeconomic analysis of an evaporative desiccant air-conditioning system.

Auteurs : CAMARGO J. R., EBINUMA C. D., SILVERA J. L.

Type d'article : Article

Résumé

This paper presents a thermoeconomic analysis method based on the first and second law of thermodynamics and applied to an evaporative cooling system coupled to an adsorption dehumidifier. The main objective is to use a method called exergetic manufacturing cost (EMC) applied to a system that operates in three different conditions to minimize the operation costs. Basic parameters are the R/P ratio (reactivation air/process air) and the reactivation air temperature. Results of this work show that the minimum reactivation temperature and the minimum R/P ratio corresponds to the smaller EMC. This result can be corroborated through energetic analysis. It was noted that this case is also that which corresponds to lower energy loss.

Détails

  • Titre original : Thermoeconomic analysis of an evaporative desiccant air-conditioning system.
  • Identifiant de la fiche : 2004-0823
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 23 - n. 12
  • Date d'édition : 08/2003

Liens


Voir d'autres articles du même numéro (7)