Analysis of the performance characteristics of a refrigeration system operating on contaminated R404A refrigerant.

Numéro : 0766

Auteurs : GIL B.

Résumé

The study conducted presents the performance of the refrigeration system operating with non-regenerated R404A and additionally contaminated with R32. Experimental studies of the refrigeration cycle have shown that a relatively small addition of R32 leads to significant changes in the system pressure analyzed. There is also a noticeable change in the compressor suction temperature, which for the averaged cycle is 6 K lower than for R404A. The reduction of the evaporating temperature and the deterioration of the heat exchange conditions lead to a reduction of the vapor superheat and, in long-term operation, to the appearance of liquid in the compressor suction line. Therefore, the advantages obtained by changing the composition of the refrigerant can only be obtained by a deliberate intervention, preceded each time by an analysis of the functioning of the cycle and the adjustment of its elements. Failure to do so may result in serious malfunction.

Documents disponibles

Format PDF

Pages : 10

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Analysis of the performance characteristics of a refrigeration system operating on contaminated R404A refrigerant.
  • Identifiant de la fiche : 30031876
  • Langues : Anglais
  • Sujet : Technologie
  • Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
  • Date d'édition : 21/08/2023
  • DOI : http://dx.doi.org/10.18462/iir.icr.2023.0766

Liens


Voir d'autres communications du même compte rendu (491)
Voir le compte rendu de la conférence