Document IIF

Banc d'essais pour un système frigorifique à multi-éjecteur au R744.

Test facility for a multiejector R744 refrigeration system.

Numéro : pap. ID70

Auteurs : BANASIAK K., HAFNER A., HADDAL O., et al.

Résumé

A test facility for experimental investigation of a new multiejector R744 refrigeration system was designed and manufactured. An expansion/pre-compression block consisting of multiple ejectors was introduced into the parallel compression system, partially substituting for a classic high pressure valve. The ejectors, operated for both vapor and liquid pre-compression, in parallel or individually, entrain refrigerant from the suction accumulator at low pressure (28 bar - 32 bar) and transport it to the liquid receiver at the intermediate pressure (34 bar - 38 bar). The preliminary experimental results reported individual ejector efficiencies up to 30%, dependent on operational conditions (discharge pressure and temperature, pressure lift, evaporation pressure).

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Test facility for a multiejector R744 refrigeration system.
  • Identifiant de la fiche : 30012652
  • Langues : Anglais
  • Source : 11th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2014). Proceedings. Hangzhou, China, August 31-September 2, 2014.
  • Date d'édition : 02/08/2014

Liens


Voir d'autres communications du même compte rendu (119)
Voir le compte rendu de la conférence