Calcul de la longueur maximale d’un conduit de refroidissement enterré directement dans une station urbaine de refroidissement.

[In Chinese. / En chinois.]

Auteurs : TAN C., HU H., ZHANG C., et al.

Type d'article : Article

Résumé

Based on the thermal balance among the allowed temperature increase of the supply water and return water when the energy efficiency of the chiller degrades,the heat transfer of the pipehne and the heat from the friction of electric motors,deduces the mathematical expression of the maximum length of the directly buried cooling pipeline in the district cooling base station.The results show that the insulation layer is needed for the directly buried pipeline in engineering application with a thickness of 0.04 meter appropriately,which ensures a maximum pipeline length of 930 to 1 400 meters.

Documents disponibles

Format PDF

Pages : 30-33, 37