Calcul des pertes de charge d'un frigoporteur.

Il calcolo delle perdite di carico di un fluido secondario.

Auteurs : GRAZZINI G., FERRARO P.

Type d'article : Article

Résumé

Despite the opinion of some investigators, the presence of ice crystals in a coolant always increases pressure losses and, consequently, the energy requirements of pumps. Regarding two-phase ethylene glycol-ice mixtures, the errors made by using the Darcy-Weisbach formula, in combination with the Blasius formula, are of the same order of magnitude as the differences between the correlation results obtained from various direct experiments on two-phase mixtures. The formulae normally used for the calculation of pump power input with single-phase mixtures can be used with two-phase mixtures, obviously on the condition that the relevant physical parameters of the diphasic mixture are taken into account.

Détails

  • Titre original : Il calcolo delle perdite di carico di un fluido secondario.
  • Identifiant de la fiche : 2000-2532
  • Langues : Italien
  • Source : Zero sotto Zero - vol. 8 - n. 4
  • Date d'édition : 05/1999
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (2)
Voir la source