Caractéristiques du givrage et du transfert de chaleur sur une plaque plate dans des conditions de fonctionnement givrant. 2. Modélisation numérique et comparaison avec des données.

Frost characteristics and heat transfer on a flat plate under freeze operating conditions. 2. Numerical modelling and comparison with data.

Résumé

An existing numerical model for frost growth as a porous media is modified to include boundary conditions for a relatively high-density frost layer adjacent to a cold plate and turbulent airflow over a rough frost-air interface. Low-density frost grows on top of this high-density surface layer. Simulation results compare well with the data for selected test conditions where experimental uncertainty is small. When the experimental uncertainty is small, a validated physical/numerical model may be the best means of interpreting the physical nature of frost growth and extrapolating a limited database for frost growth.

Détails

  • Titre original : Frost characteristics and heat transfer on a flat plate under freeze operating conditions. 2. Numerical modelling and comparison with data.
  • Identifiant de la fiche : 2001-1734
  • Langues : Anglais
  • Source : ASHRAE Transactions. 1999 Annual Meeting, Seattle, Washington + CD-ROM.
  • Date d'édition : 1999
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.