Cartographies générales de la performance des pompes à chaleur résidentielles à vitesse unique ou à deux vitesses.
Generalized performance maps for single and dual speed residential heat pumps .
Numéro : pap. 2527
Auteurs : NYIKA S., HOLLOWAY S., BRAUN J. E., et al.
Résumé
This paper presents generic equipment models that capture the performance of families of similar heat pumps equipment and that can be used in building simulation programs. Mapping has been carried out for families of single and dual compressor speed ducted split systems and the correlations are being implemented as components for building simulation. The units mapped ranged in nominal capacity from 1 to 5 tons (3.5 - 17.6 kW) and 2 tons to 5 tons (7.0-17.6 kW) for the single and dual speed units, respectively. Equipment models for building simulation were generated based on the ASHRAE secondary toolkit direct expansion model. Single sets of correction factor equations were found for each family in heating mode and cooling mode by first aggregating normalized performance data of all the units in each family and then mapping the normalized performance characteristics using the ASHRAE toolkit model (Brandemuehl, 1993). The dual speed unit model was split into two parts; one set of coefficients for low speed and another for high compressor speed. These models are based on modern equipment currently on the market and provide a useful update to the currently available standard direct expansion air conditioner models in building simulation programs. The generalized models generated in this study were compared to established performance models based on the ASHRAE toolkit model for cooling and the DOE 2.1 RESYS routine for heating mode operation.
Documents disponibles
Format PDF
Pages : 10 p.
Disponible
Prix public
20 €
Prix membre*
15 €
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Generalized performance maps for single and dual speed residential heat pumps .
- Identifiant de la fiche : 30006432
- Langues : Anglais
- Source : 2012 Purdue Conferences. 14th International Refrigeration and Air-Conditioning Conference at Purdue.
- Date d'édition : 16/07/2012
Liens
Voir d'autres communications du même compte rendu (195)
Voir le compte rendu de la conférence
Indexation
-
PROBABILITES D'UTILISATION DES POMPES A CHALEUR...
- Auteurs : DITTMANN A., HOFMANN H., SCHÄFER W.
- Date : 1981
- Langues : Allemand
- Source : Energietechnik - vol. 31 - n. 12
Voir la fiche
-
Solar heat pump systems for heating application...
- Auteurs : POPPI S.
- Date : 09/10/2017
- Langues : Anglais
- Formats : PDF
Voir la fiche
-
Study on a solar hybrid heat pump system using ...
- Auteurs : KIM W. S., OH J., PARK C., et al.
- Date : 21/08/2011
- Langues : Anglais
- Source : Proceedings of the 23rd IIR International Congress of Refrigeration: Prague, Czech Republic, August 21-26, 2011. Overarching theme: Refrigeration for Sustainable Development.
- Formats : PDF
Voir la fiche
-
LA POMPE A CHALEUR (TEMPLIFIER).
- Auteurs : FRIGERIO G.
- Date : 1981
- Langues : Italien
- Source : Termotecnica - vol. 35 - n. 9
Voir la fiche
-
L'APPLICATION DE LA POMPE A CHALEUR DANS LES LO...
- Auteurs : VILLAUME M.
- Date : 1981
- Langues : Français
- Source : Rev. gén. Froid - vol. 71 - n. 4
Voir la fiche