Document IIF

Charge frigorifique, chute de pression et transfert de chaleur lors de la condensation dans des tubes aplatis.

Refrigerant charge, pressure drop, and condensation heat transfer in flattened tubes.

Auteurs : WILSON M. J., NEWELL T. A., CHATO J. C., et al.

Résumé

The purpose of the study was to explore the refrigerant side flow characteristics inside flattened tubes. Some of the findings for flat tubes are: significant reduction in refrigerant mass; pressure drop results scale with hydraulic diameter; microfin pressure drop effects can be modelled with equivalent roughness factors; very high heat transfer enhancement in microfin tubes. The downside of flattening a tube is the increased pressure drop penalty. For practical applications, heat exchanger and system manufacturers must take into account more detailed economic considerations.

Documents disponibles

Format PDF

Pages : 2001-5

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Refrigerant charge, pressure drop, and condensation heat transfer in flattened tubes.
  • Identifiant de la fiche : 2003-0642
  • Langues : Anglais
  • Source : Thermophysical Properties and Transfer Processes of New Refrigerants.
  • Date d'édition : 03/10/2001

Liens


Voir d'autres communications du même compte rendu (60)
Voir le compte rendu de la conférence