Document IIF

Chute de pression durant la condensation de mélanges de frigorigènes à proximité de la pression critique.

Pressure drop during near-critical-pressure condensation of refrigerant blends.

Auteurs : ANDRESEN U. C., GARIMELLA S., MITRA B., et al.

Type d'article : Article, Article de la RIF

Résumé

This paper presents the results of an experimental study on pressure drop during condensation of refrigerant blends R404A and R410A at near-critical pressures inside tubes of 0.76?=?D?=?9.4?mm. Local frictional pressure gradients were measured at reduced pressures (Pr) of 0.8 and 0.9 for the mass flux range 200?=?G?=?800?kg m-2?s-1, in small quality increments. The data were compared with adiabatic and diabatic two-phase pressure drop correlations from the literature. These correlations were not able to adequately predict the pressure drop over the range of tube sizes and mass fluxes under consideration here at high reduced pressures. A new correlation for pressure drop is introduced, which accounts for property variations and microchannel effects. The correlation predicts 85% of the data within ±25%, with an average deviation between model predictions and data of ±14%.

Documents disponibles

Format PDF

Pages : 1-13

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Pressure drop during near-critical-pressure condensation of refrigerant blends.
  • Identifiant de la fiche : 30016266
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 59
  • Date d'édition : 11/2015

Liens


Voir d'autres articles du même numéro (27)