Résumé
The pressure drop characteristic experiments of R410A through short tube orifices (diameter ranged from 0.7 to 1 mm, and length ranged from 5 to 15 mm) were performed under specific condensing pressure, evaporating pressure and sub-cooling degree conditions. A quadratic regression semi-empirical benchmark model was established based on the impedance calculation method. According to the benchmark model, the pressure drop characteristic experiments were performed under condensing pressures ranged from 2500 to 3100 kPa, evaporating pressures ranged from 900 to 1200 kPa and sub-cooling degrees ranged from 3 to 9 °C. A semi-empirical universal model of pressure drop characteristic of R410A through short tube orifices is developed. The model can cover the test range of working conditions and refrigerant mass flow rate. The model is used to predict the pressure drop of R410A through two kinds of the short tube orifices under a variety of working conditions, and the deviation between the predicted value and the measured value is within ±10%. The experimental results of air conditioner matching validation experiments show that the air conditioning system don’t need to adjust with the short tube orifices replace the capillary tubes.
Détails
- Titre original : Experimental investigation on pressure drop characteristic of R410A through short tube orifices.
- Identifiant de la fiche : 30019860
- Langues : Anglais
- Source : Applied Thermal Engineering - vol. 109, part A
- Date d'édition : 25/10/2016
- DOI : http://dx.doi.org/10.1016/j.applthermaleng.2016.07.038
Liens
Voir d'autres articles du même numéro (7)
Voir la source
Indexation
-
Thèmes :
Mesures thermodynamiques;
HFC - Mots-clés : R410A; Conditionneur d'air; Tube; Orifice; Experimentation; Chute de pression
-
Flow pattern, mass flow rate, pressure distribu...
- Auteurs : NILPUENG K., SUPAVARASUWAT C., WONGWISES S.
- Date : 12/2009
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 32 - n. 8
- Formats : PDF
Voir la fiche
-
Pressure drop during near-critical-pressure con...
- Auteurs : ANDRESEN U. C., GARIMELLA S., MITRA B., et al.
- Date : 11/2015
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 59
- Formats : PDF
Voir la fiche
-
Chute de pression de l'écoulement diphasique va...
- Auteurs : ENOKI K., MORI H., MIYATA K., et al.
- Date : 2013
- Langues : Japonais
- Source : Transactions of the Japan Society of Refrigerating and Air Conditioning Engineers - vol. 30 - n. 4
Voir la fiche
-
Two phase pressure drop in microchannels.
- Auteurs : NIÑO V., PAYNE W., HRNJAK P., et al.
- Date : 03/10/2001
- Langues : Anglais
- Source : Thermophysical Properties and Transfer Processes of New Refrigerants.
- Formats : PDF
Voir la fiche
-
Convective boiling pressure drop of refrigerant...
- Auteurs : BANDARRA FILHO E. P., SAIZ JABARDO J. M., BARBIERI P. E. L.
- Date : 12/2004
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 27 - n. 8
- Formats : PDF
Voir la fiche