Clapets d'expansion électroniques pour des systèmes frigorifiques industriels.

[In Japanese. / En japonais.]

Auteurs : OMATA S., OKAMOTO K., UEDA S.

Type d'article : Article

Résumé

The paper reports on the difference in performance between the electronic expansion valve (EEV) and the conventional thermostatic valve (TEV) when used for evaporation in a cold store. The experiment consisted of a comparison test with mechanical refrigeration using an ammonia vapour compression cycle. The result of the experiment showed that the EEV can cool down cold stores in 76% less time than the TEV. Energy consumption used to keep the refrigeration runing at -24 deg C decreased by approximately 30% when using the EEV, compared to the TEV. The authors estimate that the initial cost may be recovered in less than two years.

Détails

  • Titre original : [In Japanese. / En japonais.]
  • Identifiant de la fiche : 1998-2265
  • Langues : Japonais
  • Source : Refrigeration - vol. 72 - n. 837
  • Date d'édition : 07/1997
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (3)
Voir la source