COEFFICIENTS DE TRANSFERT DE CHALEUR PAR EVAPORATION ET CONDENSATION POUR LE MELANGE R124-R22-R152A ET POUR LE R12.

EVAPORATION AND CONDENSATION HEAT TRANSFER COEFFICIENTS FOR A HCFC-124/HCFC-22/HFC-152A BLEND AND CFC-12.

Résumé

ON RAPPORTE LES COEFFICIENTS DE TRANSFERT DE CHALEUR EXPERIMENTAUX POUR UN MELANGE TERNAIRE DE FRIGORIGENES COMPOSE DE 40 % DE R124, DE 36 % DE R22 ET DE 24 % DE R152A. CE MELANGE POURRAIT CONSTITUER UN REMPLACANT POSSIBLE DU R12, DANS DES CYCLES FRIGORIFIQUES A COMPRESSION DE VAPEUR. ON A DETERMINE LES COEFFICIENTS DE TRANSFERT DE CHALEUR DANS UN TUBE LISSE HORIZONTAL. ON A CONSTATE QUE LES COEFFICIENTS DU MELANGE ETAIENT SUPERIEURS DE 12 A 35 %, POUR L'EVAPORATION, ET DE 12 A 30 % POUR LA CONDENSATION, SI ON COMPARAIT A DES FLUX MASSIQUES SIMILAIRES. LA COMPARAISON D'UN CYCLE FRIGORIFIQUE POUR LE MELANGE ET D'UN CYCLE FRIGORIFIQUE POUR LE R12, ASSURANT DES PUISSANCES FRIGORIFIQUES SIMILAIRES, MONTRE QUE L'ON A UN DEBIT DU MELANGE INFERIEUR DANS L'EVAPORATEUR ET DANS LE CONDENSEUR PARCE QUE L'ENTHALPIE DE VAPORISATION EST SUPERIEURE. A UNE PUISSANCE FRIGORIFIQUE IDENTIQUE, DANS L'EVAPORATEUR, LE RAPPORT DES COEFFICIENTS DE TRANSFERT DE CHALEUR QU'A UNE PUISSANCE DE CHAUFFAGE SIMILAIRE, DANS LE CONDENSEUR, LE RAPPORT EST DE 0,98 A 1,05.

Détails

  • Titre original : EVAPORATION AND CONDENSATION HEAT TRANSFER COEFFICIENTS FOR A HCFC-124/HCFC-22/HFC-152A BLEND AND CFC-12.
  • Identifiant de la fiche : 1991-1070
  • Langues : Anglais
  • Date d'édition : 17/07/1990
  • Source : Source : USNC-IIR/Proc. 1990 Refrig. Conf., Purdue Univ./ASHRAE, Purdue CFC Conf./Purdue Univ., Ray W. Herrick Lab., Sch. mech. Eng.
    234-241; 5 fig.; 2 tabl.; 12 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.