COMPARAISON EXPERIMENTALE DES COEFFICIENTS DE TRANSFERT DE CHALEUR LORS DE L'EVAPORATION ET DE LA CONDENSATION, POUR LE R134A ET LE R12.

AN EXPERIMENTAL COMPARISON OF EVAPORATION AND CONDENSATION HEAT TRANSFER COEFFICIENTS FOR HFC-134A AND CFC-12.

Résumé

ON A MESURE LES COEFFICIENTS DE TRANSFERT DE CHALEUR DANS UN TUBE LISSE ET HORIZONTAL. LE FRIGORIGENE, DANS LE TUBE D'ESSAI, A ETE CHAUFFE OU REFROIDI PAR ECOULEMENT D'EAU DANS L'ESPACE ANNULAIRE AUTOUR DU TUBE. LES ESSAIS SUR L'EVAPORATION ONT ETE EFFECTUES POUR UNE PLAGE DE TEMPERATURES COMPRISES ENTRE 278 ET 288 K (5 ET 15 DEG C), AVEC DES TITRES DE VAPEUR A L'ENTREE ET A LA SORTIE DE 10 ET 90 %, RESPECTIVEMENT. POUR LES ESSAIS SUR LA CONDENSATION, LA TEMPERATURE ALLAIT DE 303 A 323 K (30 A 50 DEG C), AVEC DES TITRES DE VAPEUR A L'ENTREE ET A LA SORTIE DE 90 ET 10 %, RESPECTIVEMENT. POUR DES FLUX MASSIQUES SIMILAIRES, LES COEFFICIENTS DE TRANSFERT DE CHALEUR POUR LE R134A ONT ETE CONSIDERABLEMENT SUPERIEURS A CEUX DU R12. LA COMPARAISON DES CYCLES DE REFROIDISSEMENT AVEC DU R134A OU DU R12 MONTRE QUE LE R134A PRESENTE UN DEBIT MASSE INFERIEUR PARCE QUE L'ENTHALPIE DE VAPORISATION EST SUPERIEURE.

Détails

  • Titre original : AN EXPERIMENTAL COMPARISON OF EVAPORATION AND CONDENSATION HEAT TRANSFER COEFFICIENTS FOR HFC-134A AND CFC-12.
  • Identifiant de la fiche : 1991-1069
  • Langues : Anglais
  • Date d'édition : 17/07/1990
  • Source : Source : USNC-IIR/Proc. 1990 Refrig. Conf., Purdue Univ./ASHRAE, Purdue CFC Conf./Purdue Univ., Ray W. Herrick Lab., Sch. mech. Eng.
    215-224; 5 fig.; 2 tabl.; 12 ref.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.