Combinaison de l’échange de chaleur actif et de la déshumidification membranaire sous vide de l’air pour un conditionnement d’air à haute efficacité.
Coupling active heat exchange and vacuum membrane-based air dehumidification for high-efficiency air conditioning.
Auteurs : FIX A. J.
Type de monographie : Thèse de doctorat
Résumé
Building cooling and ventilation account for nearly 10% of the global electricity consumption. In fact, a recent study even showed that, globally, dehumidification consumes more energy than sensible cooling. One high-efficiency dehumidification technology is selective membrane dehumidification. Selective membranes allow water vapor transport but block air transport. There are two overarching gaps in the literature that are addressed in this dissertation: (1) vacuum membrane dehumidification (VMD) has been rigidly defined as an isothermal process and (2) literature on one of the most efficient VMD system designs, which I will refer to as the “dual module humidity pump,” is limited to ideal thermodynamic modeling (no experimental demonstration or practical system modeling in the current literature).
This work presents a novel system concept, referred to as the “Active Membrane Energy Exchanger” (AMX), which specifically couples VMD and air cooling into one process to provide the first non-isothermal VMD system concept. The present study provides a wholistic understanding of the benefits and limitations of the AMX approach through both thermodynamic system modeling and experimental protype development and demonstration.
System models developed in Engineering Equation Solver were used to compare the energy performance of the AMX to other HVAC technologies. These models showed that the AMX could achieve up to 25% annual cooling electricity savings in commercial buildings and up to 60% annual cooling electricity savings in 100% outdoor air applications. Experiments showed that combining cooling and dehumidification increased membrane permeance by up to 40% and increased dehumidification performance by 3-6%. Further demonstration showed the prototype could remove up to 45% of the humidity in the humid air flow but struggled to reject all of that vapor to the exhaust air (mass transfer imbalance). This discovery enabled a practical thermofluid model to estimate theoretical and practical COP limits, which were approximately 40 and 10, respectively. Additionally, a global sensitivity analysis on the new model showed that mechanical design is far more limiting to the performance than material design.
In summary, this dissertation develops and demonstrates a novel air conditioning technology, from system modeling to prototype demonstration. This work was funded and guided by industry partners, and the results of this dissertation are a major step towards real-world implementation.
Documents disponibles
Format PDF
Pages : 247 p.
Disponible
Gratuit
Détails
- Titre original : Coupling active heat exchange and vacuum membrane-based air dehumidification for high-efficiency air conditioning.
- Identifiant de la fiche : 30033139
- Langues : Anglais
- Sujet : Technologie
- Édition : Purdue University
- Date d'édition : 12/2023
- DOI : http://dx.doi.org/https://doi.org/10.25394/PGS.24665763.v1
Indexation
-
Thèmes :
Conditionnement d'air pour le confort;
Efficacité energétique, économie d'énergie;
Equipements d'humidification/déshumidification - Mots-clés : Conditionnement d'air; Modélisation; Prototype; Membrane; Déshumidification; Application commerciale; Consommation d'énergie; Économie d'energie; Cycle thermodynamique; Experimentation; Performance
-
Empirical Analysis of Dehumidification Performa...
- Auteurs : CHEON S.-Y., CHO H. J., KO J., JEONG J. W.
- Date : 31/08/2021
- Langues : Anglais
- Source : 13th IEA Heat Pump Conference 2021: Heat Pumps – Mission for the Green World. Conference proceedings [full papers]
- Formats : PDF
Voir la fiche
-
Impact of mechanical ventilation and indoor air...
- Auteurs : FIX A., BRAUN J., WARSINGER D.
- Date : 05/2021
- Langues : Anglais
- Source : 2021 Purdue Conferences. 18th International Refrigeration and Air-Conditioning Conference at Purdue.
- Formats : PDF
Voir la fiche
-
Mejora del rendimiento de equipos de aire acond...
- Auteurs : VELAZQUEZ A., JUAN MARTINEZ P., MARTINEZ P.
- Date : 11/11/2020
- Langues : Espagnol
- Source : X Congreso Ibérico y VIII Congreso Iberoamericano de Ciencias y Técnicas del Frío, CYTEF 2020.
- Formats : PDF
Voir la fiche
-
A performance analysis of the Claridge-Culp-Liu...
- Auteurs : CLARIDGE D. E., CULP C. H., PATE M., HABERL J., BYNUM J., TANSKYI O., SCHAFF F.
- Date : 02/2021
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 122
- Formats : PDF
Voir la fiche
-
Utilization of hybrid air conditioner and ultra...
- Auteurs : YANG Z., SHI W., WANG B., XIAO H., LIN B.
- Date : 21/08/2023
- Langues : Anglais
- Source : Proceedings of the 26th IIR International Congress of Refrigeration: Paris , France, August 21-25, 2023.
- Formats : PDF
Voir la fiche