Document IIF

Combustion diesel d'un mélange d'huile et de frigorigène pendant la vidange de conditionneurs d'air.

Diesel combustion of oil and refrigerant mixture during pump-down of air conditioners.

Numéro : pap. n. 453

Auteurs : HIGASHI T., SAITOH S., DANG C. B., et al.

Résumé

In this study, we aimed to reproduce the diesel combustion that may occur during the pump-down of air conditioners and measured the pressure inside the compressor when this combustion occurred. As refrigerants, we examined R1234yf, R32, R410A, R134a, R22, and R125, and investigated different combinations of refrigerants and lubricating oil by changing the refrigerant concentration. We determined that the combustion accidents that may occur during pump-down are caused by the diesel combustion of the air, refrigerant, and oil mixture even though the refrigerant is categorized as being non-flammable.

Documents disponibles

Format PDF

Pages : 8 p.

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Diesel combustion of oil and refrigerant mixture during pump-down of air conditioners.
  • Identifiant de la fiche : 30015889
  • Langues : Anglais
  • Source : Proceedings of the 24th IIR International Congress of Refrigeration: Yokohama, Japan, August 16-22, 2015.
  • Date d'édition : 16/08/2015
  • DOI : http://dx.doi.org/10.18462/iir.icr.2015.0453

Liens


Voir d'autres communications du même compte rendu (657)
Voir le compte rendu de la conférence