Commande prédictive pour l'amélioration des performances d'un système de chauffage par pompe à chaleur aérothermique via une différence de température variable de l'eau.

Model predictive control for the performance improvement of air source heat pump heating system via variable water temperature difference.

Auteurs : WANG W., HU B., WANG R. Z., LUO M., ZHANG G., XIANG B.

Type d'article : Article de la RIF

Résumé

The heat pump heating system has been widely accepted to provide space and water heating in commercial and residential buildings. However, the operating energy performance in practice conditions is limited due to the traditional control strategy. An efficient-cost advanced control strategy is desired to improve the overall operating performance. This paper presents a model predictive control (MPC) strategy for an air source heat pump (ASHP) heating system to optimize the overall operating performance. Based on the control-oriented model and objective function, MPC can provide the optimized compressor frequency and water mass flow rate in real-time, which can lead to the optimized real-time variable water temperature difference. Thus, the total power consumption can be minimized for the heating system by coordinating the compressor power consumption and water pump power consumption in the real-time operating condition. A high-fidelity physical model is first built to produce the required data source, and then the control-oriented model is derived based on the machine learning technique. MPC is designed to minimize the total power consumption providing that the heating capacity is well maintained. The MPC strategy is evaluated and compared with the traditional PI control method under three operating cases.
Previous article in issue

Documents disponibles

Format PDF

Pages : 169-179

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Model predictive control for the performance improvement of air source heat pump heating system via variable water temperature difference.
  • Identifiant de la fiche : 30029621
  • Langues : Anglais
  • Sujet : Technologie
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 138
  • Date d'édition : 06/2022
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2022.03.001
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (20)