Comparaison de la performance lors de l'évaporation de R22, R134a, R410A et R407C dans des tubes lisses et à surface augmentée. 2. Chute de pression.
A comparison of R22, R134a, R410A, and R407C condensation performance in smooth and enhanced tubes. 2. Pressure drop.
Auteurs : ECKELS S. J., TESENE B. A.
Résumé
Pressure drops are reported at four mass fluxes, at two saturation temperatures, and over a range of average qualities in the test tubes. The pressure drops for R410A were approximately 40% lower than those of R22 in both tubes. R407C had 10 to 20% lower pressure drops than R22, while R134a had slightly larger pressure drops than R22.
Détails
- Titre original : A comparison of R22, R134a, R410A, and R407C condensation performance in smooth and enhanced tubes. 2. Pressure drop.
- Identifiant de la fiche : 2001-1722
- Langues : Anglais
- Source : ASHRAE Transactions. 1999 Annual Meeting, Seattle, Washington + CD-ROM.
- Date d'édition : 1999
- Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.
Liens
Voir d'autres communications du même compte rendu (57)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HCFC;
HFC;
Transfert de masse;
Mélanges - Mots-clés : Circuit frigorifique; R410A; R407C; R134a; Surface augmentée; Comparaison; Tube lisse; R22; Condensation; Chute de pression
-
Flow pattern-based pressure drop correlations f...
- Auteurs : LIEBENBERG L., OLIVIER J., THOME J. R., et al.
- Date : 02/08/2005
- Langues : Anglais
- Source : Commercial Refrigeration. Thermophysical Properties and Transfer Processes of Refrigerants. Proceedings of the IIR International Conferences.
- Formats : PDF
Voir la fiche
-
In-tube condensation of R134a, R22, R407C and R...
- Auteurs : NESHAN M., THORS P., TZUOO S. M.
- Date : 17/08/2003
- Langues : Anglais
- Source : 21st IIR International Congress of Refrigeration: Serving the Needs of Mankind.
- Formats : PDF
Voir la fiche
-
A comparison of R22, R134a, R410A, and R407C co...
- Auteurs : ECKELS S. J., TESENE B. A.
- Date : 1999
- Langues : Anglais
- Source : ASHRAE Transactions. 1999 Annual Meeting, Seattle, Washington + CD-ROM.
Voir la fiche
-
Nucleate boiling performance of R22, R123, R134...
- Auteurs : WANG C. C., SHIEH W. Y., CHANG Y. J.
- Date : 1998
- Langues : Anglais
- Source : ASHRAE Transactions. 1998 Winter Meeting, San Francisco, CA.
Voir la fiche
-
Condensation of refrigerants in horizontal micr...
- Auteurs : WANG H. S., ROSE J. W., HONDA H.
- Date : 06/2003
- Langues : Anglais
- Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 26 - n. 4
- Formats : PDF
Voir la fiche