Comparaison des performances des systèmes à absorption à double effet et à eau-bromure de lithium à écoulement parallèle ou en série.

Performance comparison of double-effect parallel-flow and series flow water-lithium bromide absorption systems.

Auteurs : ARUN M. B., MAIYA M. P., MURTHY S. S.

Type d'article : Article

Résumé

The double-effect parallel flow absorption refrigeration cycle with water-lithium bromide as working fluid is analysed based on the concept of equilibrium temperature at the low pressure generator. COP and its sensitivity to operating conditions are compared with those for series flow cycle. Maximum attainable COP for parallel flow cycle is greater than that for series flow cycle throughout the range of operating conditions considered in the article. Performance of parallel flow system is more sensitive to the effectiveness of low pressure heat exchanger than that of series flow system.

Détails

  • Titre original : Performance comparison of double-effect parallel-flow and series flow water-lithium bromide absorption systems.
  • Identifiant de la fiche : 2002-1849
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 21 - n. 12
  • Date d'édition : 08/2001

Liens


Voir d'autres articles du même numéro (4)
Voir la source