Résumé
We present a comparison of the R-404A, R-448A and R-452A as drop-in replacements for R-218 refrigerant in high-tech electronics cooling. The tests were carried out in an oil-less experimental circuit originally designed for cooling of silicon chips with R-218. The circuit is equipped with tens of temperature, pressure and flow sensors and precise liquid and vapour pressure control. The same capillary was used for all the tested refrigerants providing mass flow of 1.2 g/s. Two-stage compression allowed to test suction pressures from 0.5-1 bar absolute. The aim was to evaluate the possibility of replacing the rarely used, expensive and environment unfriendly R-218 by more ecological blends while achieving lower evaporation temperature and without hardware modifications to the existing circuit layout. The results are applicable to low temperature systems with commercial two-stage reciprocating compressors that are being converted from R-404A to ecological alternatives R-448A/R-449A or R-452A.
Documents disponibles
Format PDF
Pages : 8
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Comparison of R-404A, R-448A and R-452A as drop-in replacements for R-218 in special applications.
- Identifiant de la fiche : 30026034
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Date d'édition : 24/08/2019
- DOI : http://dx.doi.org/10.18462/iir.icr.2019.0804
Liens
Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HFC;
Mélanges - Mots-clés : R218; Électronique; Remplacement immediat; R452A; R448a; R404A; Substitut; Mélange; Essai; Frigorigène; Congélateur
-
Automatic calorimeter for mixed refrigerants.
- Auteurs : PEARSON S. F.
- Date : 20/08/1995
- Langues : Anglais
- Source : For a Better Quality of Life. 19th International Congress of Refrigeration.
- Formats : PDF
Voir la fiche
-
System drop-in tests of refrigerant blend R125-...
- Auteurs : SNELSON W. K., LINTON J. W., TRIEBE A. R., HEARTY P. F.
- Date : 01/1995
- Langues : Anglais
- Source : ASHRAE Transactions.
Voir la fiche
-
Low GWP drop-in alternative refrigerants for lo...
- Auteurs : VAITKUS L., BALCIUS A.
- Date : 11/04/2022
- Langues : Anglais
- Source : 7th IIR International Conference on Sustainability and the Cold Chain (Online). Proceedings: April 11-13 2022
- Formats : PDF
Voir la fiche
-
Mixture of HFC-134a and HC-600a: a promising su...
- Auteurs : CHAUBE A., AGARWAL R. S.
- Date : 18/03/1998
- Langues : Anglais
- Source : Emerging trends in refrigeration and air-conditioning.
- Formats : PDF
Voir la fiche
-
Replacement of R-404A refrigerant in supermarkets.
- Auteurs : CALMELS O., MICHINEAU T., SUQUET T.
- Date : 24/08/2019
- Langues : Anglais
- Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
- Formats : PDF
Voir la fiche