COMPARAISON DU R134A ET DU R12.

[In Serbo-Croat. / En serbo-croate.]

Auteurs : PETERSSON B., THORSELL H.

Type d'article : Article

Résumé

ON A EFFECTUE UNE COMPARAISON DU R134A ET DU R12, ET, DANS CET ARTICLE, ON RAPPORTE LES RESULTATS D'UNE ANALYSE THEORIQUE ET D'ESSAIS EFFECTUES AVEC UN COMPRESSEUR A PISTON OUVERT. LE COMPRESSEUR ESSAYE A PRESENTE UNE MEILLEURE CAPACITE FRIGORIFIQUE AVEC LE R134A QU'AVEC LE R12, DANS CERTAINES CONDITIONS DE FONCTIONNEMENT. CEPENDANT, LES RESULTATS INDIQUENT AUSSI UNE PUISSANCE ELECTRIQUE ABSORBEE ACCRUE DU COMPRESSEUR, SUR TOUTE LA PLAGE DE TEMPERATURES. LA CONSEQUENCE EST UNE BAISSE DU COP. UNE AUTRE CONSEQUENCE A NOTEREST LA DEPENDANCE DU RENDEMENT ISENTROPIQUE DU COMPRESSEUR SUR LA TEMPERATURE, LORSQU'ON UTILISE DU R134A. CELA PEUT ETRE EXPLIQUE PAR LES PROPRIETES DE L'HUILE DE POLYALKENE GLYCOL QUE L'ON UTILISE AVEC LE R134A. LE COUT ELEVE DU R134A SE JUSTIFIE SI L'ON CONSIDERE LES ASPECTS ENVIRONNEMENTAUX ET SI L'ON PEUT RESOUDRE LES PROBLEMES PRATIQUES TELS QUE L'INFLUENCE SUR LES MATERIAUX DU CIRCUIT FRIGORIFIQUE.

Détails

  • Titre original : [In Serbo-Croat. / En serbo-croate.]
  • Identifiant de la fiche : 1992-0513
  • Langues : Serbo-croate
  • Source : KGH (Klimatizacija Grejanje Hladenje) - vol. 20 - n. 1
  • Date d'édition : 02/1991
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres articles du même numéro (4)
Voir la source