Comparaison entre l'analyse des transferts de chaleur et de masse d'un mélange binaire et l'analyse du transfert de chaleur et de masse d'un fluide pur dans la conception d'un absorbeur/désorbeur GAX.

Comparison of binary mixture heat and mass transfer analysis with single-component heat and mass transfer analysis in the design of GAX absorber/desorber.

Résumé

The GAX cycle is an elegant way of achieving higher effect performance with single-stage configuration. One of the key components of the GAX cycle is the absorber/desorber heat exchanger, which carries out internal heat recovery. The paper investigated two different models for the design of an absorber/desorber in the GAX system. The results show that about 57% of extra heat transfer area would be needed under the case being investigated if the fluid is considered as a binary mixture rather than a single-component fluid. The paper provides a basic guideline for designing a properly sized GAX absorber-desorber.

Détails

  • Titre original : Comparison of binary mixture heat and mass transfer analysis with single-component heat and mass transfer analysis in the design of GAX absorber/desorber.
  • Identifiant de la fiche : 2001-0765
  • Langues : Anglais
  • Source : ASHRAE Transactions. 2000 Winter Meeting, Dallas, Texas + CD-ROM.
  • Date d'édition : 2000
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.

Liens


Voir d'autres communications du même compte rendu (36)
Voir le compte rendu de la conférence