Comparaison expérimentale entre R152a et R134a dans une installation frigorifique équipée d'un compresseur hermétique.

Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor.

Auteurs : CABELLO R., SÁNCHEZ D., LLOPIS R., et al.

Type d'article : Article, Article de la RIF

Résumé

The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of Global Warming. As a consequence, the refrigeration sector is moving towards refrigerants with a low Global Warming Potential (GWP100) in accordance with the limit fixed by these regulations (150). In this regard, the old refrigerant R152a attracts renewed interest due to its low GWP (138) and its similarity to R134a.
The present work shows the results of using R152a in a vapour compression plant equipped with a hermetic compressor and an IHX designed for R134a. The refrigerant was replaced by a conventional “drop-in” process in order to carry out an energy comparison. The results have revealed an improvement in the COP with R152a up to 13% despite a reduction in the cooling capacity of about 10%. During the test campaign, R134a hermetic compressors have been shown to be capable of operating with R152a.

Documents disponibles

Format PDF

Pages : 92-105

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor.
  • Identifiant de la fiche : 30016323
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 60
  • Date d'édition : 12/2015

Liens


Voir d'autres articles du même numéro (26)
Voir la source