Document IIF

Comportement dynamique d'un évaporateur à détente directe sous des conditions de givrage. I. Modèle distribué.

Dynamic behaviour of a direct expansion evaporator under frosting condition. I. Distributed model.

Auteurs : TSO C. P., CHENG Y. C., LAI A. C. K.

Type d'article : Article, Article de la RIF

Résumé

A general distributed model with two-phase flow for refrigerant coupled with a frost model is developed for studying the dynamic behaviour of an evaporator. The equations are derived in non-steady-state manner for the refrigerant and a quasi-steady state model with permeation for the frost. The complex flow and geometry of the finned tube evaporator lead to uneven wall and air temperature distributions, which in turn affect the rate of frost growth and densification along the coil depth. Results include frost accumulation and its effect on energy transfer, air off-coil temperature, refrigerant liquid dry-out position and propagation of frost formation along the coil (see also this Bulletin, reference 2006-1681).

Documents disponibles

Format PDF

Pages : 611-623

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Dynamic behaviour of a direct expansion evaporator under frosting condition. I. Distributed model.
  • Identifiant de la fiche : 2006-1677
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 29 - n. 4
  • Date d'édition : 06/2006

Liens


Voir d'autres articles du même numéro (14)
Voir la source