Document IIF

Conception de la boucle enterrée pour une pompe à chaleur sol-eau à l'Université nationale de Pusan.

Ground loop design of a ground source heat pump in Pusan national University.

Auteurs : KU B. C., JEONG Y. M., KIM G. T., et al.

Résumé

The ground source heat pump (GSHP) is installed in a building to analyze the technical and economical aspects. First of all, the heating and cooling loads were evaluated by a simulation program (Visual DOE-2) and the peak load has been calculated. In-situ thermal conductivity was measured and the ground heat exchanger was designed. The authors made a testing device for in-situ thermal conductivity measurement and the thermal conductivity was evaluated by the solution of the line source problem. Finally, the ground heat exchanger has been designed using a commercial software. The required bore length of the ground heat exchanger is 3956 m and the number of boreholes is 24 (165 m depth borehole).

Documents disponibles

Format PDF

Pages : ICR07-E2-1585

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Ground loop design of a ground source heat pump in Pusan national University.
  • Identifiant de la fiche : 2008-0906
  • Langues : Anglais
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007

Liens


Voir d'autres communications du même compte rendu (839)
Voir le compte rendu de la conférence