CONCEPTION ET MISE EN OEUVRE D'UNE INSTALLATION DE GRANDE PUISSANCE POUR LE REFROIDISSEMENT A BASSE TEMPERATURE DE L'AIR DES MINES.

THE DESIGN AND INSTALLATION OF A LARGE CAPACITY PLANT FOR LOW TEMPERATURE MINE AIR COOLING.

Résumé

LES BESOINS POUR LE SERVICE DE REFROIDISSEMENT DE L'AIR DE 293 K (20 DEG C) BULBE SEC ET 287 K (14 DEG C) BULBE HUMIDE A 279 K (6 DEG C) OU AU-DESSOUS A L'ETAT SATURE ONT AMENE A UTILISER DES COMPRESSEURS A VIS PLUTOT QUE DES COMPRESSEURS CENTRIFUGES, QUI DEVAIENT FONCTIONNER A LA PRESSION DE REFOULEMENT LA PLUS BASSE POSSIBLE. UN CONDENSEUR EVAPORATIF DE DIMENSIONS DOUBLES DES DIMENSIONS HABITUELLES A ETE PREVU POUR MAINTENIR UNE TEMPERATURE DE CONDENSATION DE 303 K (30 DEG C) A UNE TEMPERATURE DE BULBE HUMIDE DE 295 K (22 DEG C). DES EVAPORATEURS A TUBES A AILETTES EN SPIRALE ONT ETE CHOISIS AVEC DEUX COMPRESSEURS A VIS A AMMONIAC POUR LE PREMIER ETAGE ET UN POUR LE DEUXIEME ETAGE. ENVIRON 8.000 KG D'EAU SE CONDENSE A PARTIR DE L'AIR ENVOYE VERS LE BAS ET ELLE EST RECUEILLIE ET RETOURNEE AUX CONDENSEURS. L'ENSEMBLEDE LA CHARGE FRIGORIFIQUE A 295 K (22 DEG C) BULBE HUMIDE ETAIT DE 23,8 MW AVEC UNE TEMPERATURE DE L'AIR DE SORTIE DE 272,5 A IDERE AUSSI LES DIVERS ASPECTS DE LA SECURITE DE L'INSTALLATION. G.R.S.

Détails

  • Titre original : THE DESIGN AND INSTALLATION OF A LARGE CAPACITY PLANT FOR LOW TEMPERATURE MINE AIR COOLING.
  • Identifiant de la fiche : 1988-0746
  • Langues : Anglais
  • Date d'édition : 14/04/1986
  • Source : Source : Frigair '86, Pretoria
    vol. 1; n. 17; 6 p.; 2 fig.
  • Document disponible en consultation à la bibliothèque du siège de l'IIF uniquement.