Conception et recherches expérimentales sur un nouveau diffuseur d'air froid.

[In Chinese. / En chinois.]

Auteurs : ZHOU D., SHI C., XIAO B., et al.

Type d'article : Article

Résumé

A novel cold air diffuser - swirling cold air diffuser - was designed, and the experiment of this diffuser was conducted. The result shows that, with a total pressure of 24 Pa and a static pressure of 20 Pa, the induction ratio of the swirling cold air diffuser was 1.03 with low-resistance and low energy consumption. The maximum temperature difference in the tested room was 0.7°C at the plane surface and 0.4°C at the vertical surface. The range of wind velocity was 0.05-0.19 m/s and the mean wind velocity was 0.99 m/s. The air distribution performance index was 100%. In addition, the noise of the swirling cold air diffuser was 53.5 dB at the height of 1250 mm, 3 dB more than the local noise. The relative humidity of the air from the diffuser decreased by 10% and the surface of the diffuser had no condensate in the cold air conditioner.

Documents disponibles

Format PDF

Pages : 33-38

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 2009-0274
  • Langues : Chinois
  • Source : Journal of Refrigeration - vol. 29 - n. 123
  • Date d'édition : 10/2008