CONCEPTION, REALISATION ET EXPLOITATION D'UNE INSTALLATION POUR LA RECUPERATION DE CHALEUR DEGAGEE PAR UN CENTRE INFORMATIQUE A L'AIDE DE POMPES A CHALEUR ET D'INJECTION DE CALORIES DANS LE RESEAU DE CHAUFFAGE DE L'IMMEUBLE.

DESIGN, REALIZATION AND EXPLOITATION OF AN INSTALLATION FOR THE RECOVERY OF THE HEAT RELEASED IN COMPUTER CENTER BY MEANS OF HEAT PUMPS AND INJECTION OF CALORIES IN THE HEATING NETWORK OF THE BUILDING.

Résumé

L'INSTALLATION A ETE CONCUE POUR LE CONDITIONNEMENT D'AIR D'UN LOCAL DESTINE A UNEMEMOIRE CENTRALE. LA SURFACE PREVUE EST DE 640 M2 ET LA PUISSANCE THERMIQUE EST EGALE A 800 W/M2. LE CONDITIONNEMENT D'AIR A ETE REALISE PAR 5 CAISSONS DE CONDITIONNEMENT ALIMENTES AVEC DE L'EAU FROIDE A 279 K (6 DEG C). LA CHALEUR RECUPEREE EST INJECTEE DANS LE RESEAU D'EAU CHAUDE DES BATTERIES DES EJECTO-CONVECTEURS. SUIVANT LES CIRCONSTANCES, DIFFERENTES SEQUENCES DE FONCTIONNEMENT AVEC DIFFERENTES COMBINAISONS DE MACHINES THERMODYNAMIQUES SONT POSSIBLES. LE CHOIX OPTIMAL EST CALCULE PAR UN ORDINATEUR DE GESTION CENTRAL.

Détails

  • Titre original : DESIGN, REALIZATION AND EXPLOITATION OF AN INSTALLATION FOR THE RECOVERY OF THE HEAT RELEASED IN COMPUTER CENTER BY MEANS OF HEAT PUMPS AND INJECTION OF CALORIES IN THE HEATING NETWORK OF THE BUILDING.
  • Identifiant de la fiche : 1987-1995
  • Langues : Anglais
  • Sujet : Environnement
  • Date d'édition : 05/11/1986
  • Source : Source : Proc. 1st eur. Symp. Air Cond. Refrig., Brussels
    211-217; 1 fig.