Document IIF

Conception thermique et optimisation d'une pompe à chaleur à haute température intégrée au chauffage urbain au Danemark pour approvisionnement en chaleur industrielle.

Thermal design and optimization of high-temperature heat pump integrated with district heating benchmarked in Denmark for process heat supply.

Auteurs : SADEGHI M., PETERSEN T., YANG Z., ZÜHLSDORF B., MADSEN K. S.

Type d'article : Article de la RIF

Résumé

This work aims to assess and optimize the performance of cascade high-temperature heat pump (HTHP) integrated with district heating (DH) to produce 1 MW steam at 160 °C for the industrial processes. The heat available in the primary loop of the DH network at 80 °C is considered as the heat source; which is cooled down 70 °C through the HTHP evaporator, before supplying the DH secondary loop. The use of alternative hydrocarbons in the low-temperature loop are examined; and considering the gas compressor limitation, the HTHP performance of using each refrigerant is optimized and compared to each other.
The optimization results reveal that pentane- hydrocarbon with the highest critical temperature- is the most promising refrigerant to be paired with steam in the high-temperature loop, reaching the highest COP of 2.66. However, concerning safety and compressor sizing issues, butane is an excellent candidate; with volumetric heating capacity (VHC) of about two times more than that of pentane, in the expense of just about 4 % reduction in the HTHP COP. In addition, water injection theoretically controls the steam compressor discharge temperature successfully, with just 0.9 K superheating at the compressor outlet; and reduces its power consumption and the HTHP COP up to 4.3 % and 1.7 %, respectively. Moreover, techno-economic analysis demonstrates that the HTHP technology shows a better business case compared to the conventional natural gas and electric boilers.

Documents disponibles

Format PDF

Pages : 356-370

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Thermal design and optimization of high-temperature heat pump integrated with district heating benchmarked in Denmark for process heat supply.
  • Identifiant de la fiche : 30032235
  • Langues : Anglais
  • Sujet : Technologie, Alternatives aux HFC
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 159
  • Date d'édition : 03/2024
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2023.12.025

Liens


Voir d'autres articles du même numéro (32)
Voir la source