Document IIF
Condensation de vapeur saturée de R1234ze(Z) à l’intérieur d’un tube lisse horizontal de 4 mm de diamètre intérieur.
Saturated vapor condensation of R1234ze(Z) inside a 4 mm ID horizontal smooth tube.
Numéro : pap. n. 1141
Auteurs : LONGO G. A., MANCIN S., RIGHETTI G., et al.
Résumé
This is the 22 slide PowerPoint presentation of Longo, Mancin and Zilio's paper on saturated vapor condensation of R123aze(Z) inside a horizontal smooth tube. New experimental tests were carried out at 40 °C of saturation temperature, with refrigerant mass flux in the range 75–300 kg m -2 s -1 at decreasing vapour quality. The new data are then compared against some well known literature correlations and, finally, against other experimental data collected by using isobutane as two-phase fluid under the same saturation temperature and mass fluxes.
Documents disponibles
Format PDF
Pages : 22
Disponible
Gratuit
Détails
- Titre original : Saturated vapor condensation of R1234ze(Z) inside a 4 mm ID horizontal smooth tube.
- Identifiant de la fiche : 30024968
- Langues : Anglais
- Source : 1st IIR international conference on the application of HFO refrigerants, Birmingham, September 2-5 2018.
- Date d'édition : 09/2018
Liens
Voir d'autres communications du même compte rendu (126)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
Mesures thermodynamiques;
HFC - Mots-clés : Tube horizontal; Coefficient de transfert de chaleur; Vapeur; R1234ze; HFO; Experimentation; Condensation; Chute de pression