Condensation des frigorigènes à l'intérieur de tubes à micro-ailettes horizontaux : une nouvelle corrélation.

Condensation of refrigerants in horizontal microfin tubes: a new correlation.

Auteurs : WANG H. S., WEI J. J., HONDA H., et al.

Résumé

A new correlation is presented for predicting the heat-transfer coefficient during condensation of refrigerants in horizontal microfin tubes. Predicted values are compared with earlier prediction methods and with available experimental data for seven tubes and five refrigerants. The r.m.s. deviation (of relative residuals of heat-transfer coefficient) for all tubes and all refrigerants taken together was less than 11% and for the worst individual tube-refrigerant combination less than 16%.

Documents disponibles

Format PDF

Pages : ICR07-B1-658

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Condensation of refrigerants in horizontal microfin tubes: a new correlation.
  • Identifiant de la fiche : 2008-0053
  • Langues : Anglais
  • Sujet : Alternatives aux HFC
  • Source : ICR 2007. Refrigeration Creates the Future. Proceedings of the 22nd IIR International Congress of Refrigeration.
  • Date d'édition : 21/08/2007