CONDENSATION PAR CONVECTION FORCEE SUR UN TUBE HORIZONTAL. EXPERIENCES EFFECTUEES AVEC UN COURANT DE VAPEUR VERTICAL ET DESCENDANT.

FORCED CONVECTION CONDENSATION ON A HORIZONTAL TUBE. EXPERIMENTS WITH VERTICAL DOWNFLOW OF STEAM.

Auteurs : MICHAEL A. G., ROSE J. W., DANIELS L. C.

Type d'article : Article

Résumé

L'ARTICLE RAPPORTE UNE ETUDE EXPERIMENTALE SUR LA CONDENSATION DE VAPEUR S'ECOULANT VERTICALEMENT ET VERS LE BAS, SUR UN TUBE SIMPLE HORIZONTAL. DANS LE CAS DE LA VAPEUR < PURE >, LES DONNEES ONT ETE OBTENUES A LA PRESSION PRESQUE ATMOSPHERIQUE POUR DES VITESSES DE VAPEUR COMPRISES ENTRE 5 ET 81 M/S ET AVEC DES SURCHAUFFES COMPRISES ENTRE 2 ET 40 K. ON A OBSERVE QUE LES COEFFICIENTS DE TRANSFERT DE CHALEUR DU COTE DE LA VAPEUR AUGMENTAIENT AVEC LA VITESSE. POUR DES VITESSES DE VAPEUR EXCEDANT 30 M/S, LE TAUX D'AUGMENTATION DU COEFFICIENT DU COTE DE LA VAPEUR ETAIT SUPERIEUR AU TAUX PREVU PAR LA THEORIE SUR L'ECOULEMENT LAMINAIRE DU CONDENSAT. CE COMPORTEMENT A EGALEMENT ETE OBSERVE POUR LE R113 ET L'ETHYLENE GLYCOL ET POURRAIT INDIQUER LE DEBUT DE LA TURBULENCE DANS LA PELLICULE DE CONDENSAT.

Détails

  • Titre original : FORCED CONVECTION CONDENSATION ON A HORIZONTAL TUBE. EXPERIMENTS WITH VERTICAL DOWNFLOW OF STEAM.
  • Identifiant de la fiche : 1990-1823
  • Langues : Anglais
  • Source : J. Heat Transf. - vol. 111 - n. 3
  • Date d'édition : 1989