Conditionnement d'air centralisé basé sur l'adsorption et l'énergie solaire.

Central air conditioning based on adsorption and solar energy.

Auteurs : LEITE A. P. F., BELO F. A., MARTINS M. M., et al.

Type d'article : Article

Résumé

This paper presents the characterization and the pre-dimensioning of an adsorption chiller as part of a 20 kW air conditioning central unit for cooling a set of rooms that comprises an area of 110 m2. The system is basically made up of a cold water storage tank supplied by an activated carbon–methanol adsorption chiller, a hot water storage tank, fed by solar energy and natural gas, and a fan-coil. During an acclimatization of 8 h (9–17 h), the following parameters were obtained for dimensioning the cooling system: 504 kg of activated carbon, 180 L of methanol, 7000 L of hot water, 10,300 L of cold water with its temperature varying in the fan-coil from 1 to 14°C. Considering the mean value of the total daily irradiation in João Pessoa (7°8'S, 34°50'WG), and a cover of regenerating heat supplied by solar energy equivalent to 70%, the adsorption chiller’s expected coefficient of performance (COP) was found to be around 0.6. [Reprinted with permission from Elsevier. Copyright, 2010].

Détails

  • Titre original : Central air conditioning based on adsorption and solar energy.
  • Identifiant de la fiche : 30003348
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 31 - n. 1
  • Date d'édition : 01/2011
  • DOI : http://dx.doi.org/10.1016/j.applthermaleng.2010.08.010