Document IIF

Configuration alternative des groupes d’aspiration pour améliorer l’efficacité des systèmes de froid commercial au CO2 avancés.

Alternative suction groups configuration to improve efficiency of advanced CO2 commercial refrigeration systems.

Numéro : pap. 1384

Auteurs : ZHA S.

Résumé

CO2 is one of the most promising natural refrigerants in commercial refrigeration systems. A basic two-stage CO2 transcritical booster system can operate with better or comparable efficiency in cold and mild climates, compared to a traditional HFC DX system. Advanced CO2 transcritical systems, such as adding intermediate suction group (parallel compression) and parallel compression with ejectors, have been developed and installed in commercial refrigeration systems for hot climates. This paper will discuss the opportunities to additionally improve the efficiency of advanced CO2 transcritical systems by alternative configuration of suction groups: LT discharges to parallel compressor suction; Split LT suction into two different suction groups and split MT suction groups with liquid ejector. The additional system efficiency improvement is estimated to be 5-10%.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Alternative suction groups configuration to improve efficiency of advanced CO2 commercial refrigeration systems.
  • Identifiant de la fiche : 30023707
  • Langues : Anglais
  • Source : 13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018). Proceedings. Valencia, Spain, June 18-20th 2018.
  • Date d'édition : 18/06/2018
  • DOI : http://dx.doi.org/10.18462/iir.gl.2018.1384

Liens


Voir d'autres communications du même compte rendu (177)
Voir le compte rendu de la conférence