Document IIF
Conversion du HCFC-22 au NH3 : expérience pratique dans un grand centre de distribution.
Conversion from HCFC-22 to NH3: practical experiences from a large distribution centre.
Auteurs : JENSEN S., CZYCZELIS S.
Résumé
This paper details the design and installation methodologies applied during the conversion of a large existing cold storage facility from refrigerant HCFC-22 to NH3. The description follows the refrigerant conversion from initial assessment of heat loads over plant concept through to the presentation of energy consumption and maintenance records for the first two years of commercial operation after the conversion. Particular emphasis is placed on detailing the air cooler performance improvements realized as a result of the change of refrigerant and how the air coolers were converted from dry expansion HCFC-22 feed to NH3 liquid overfeed with minimal alterations to coil circuiting. Comments are provided in relation to the financial viability of the refrigerant conversion taking into account the reduction in energy consumption, the reduction in refrigerant losses and the reduction in plant maintenance costs.
Documents disponibles
Format PDF
Pages : 2008-2
Disponible
Prix public
20 €
Prix membre*
Gratuit
* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)
Détails
- Titre original : Conversion from HCFC-22 to NH3: practical experiences from a large distribution centre.
- Identifiant de la fiche : 2009-0256
- Langues : Anglais
- Source : 8th IIR-Gustav Lorentzen Conference on Natural Working Fluids (GL2008)
- Date d'édition : 07/09/2008
Liens
Voir d'autres communications du même compte rendu (132)
Voir le compte rendu de la conférence
Indexation
-
Thèmes :
HCFC;
Entrepôts frigorifiques polyvalents;
Ammoniac - Mots-clés : Recommandation; Ammoniac; R22; Substitut; Évaporateur; Entrepôt frigorifique; Conversion; Frigorigène
-
Field tests using R404A in storage refrigeration.
- Auteurs : GIRAUD A., BARREAU M.
- Date : 1999
- Langues : Anglais
- Source : Refrigerated Transport, Storage and Retail Display.
- Formats : PDF
Voir la fiche
-
Pourquoi remplacer le R22 dès aujourd'hui ?
- Auteurs : FRANCOIS S.
- Date : 19/11/2008
- Langues : Français
- Source : Journée française du froid : économie d'énergie en agroalimentaire. Recueil des conférences.
Voir la fiche
-
Alternative drop-in in refrigerant to R22 for r...
- Auteurs : BANDOH Y., FURUYAMA K., SAITO M., et al.
- Date : 04/12/2002
- Langues : Anglais
- Source : Green breeze from Asia: frontiers of refrigerants, heat transfer and system.. ACRA-2002. Proceedings of the Asian conference on refrigeration and air conditioning.
Voir la fiche
-
Conversion from R22 to R717. Practical experien...
- Auteurs : JENSEN S. S., FORBES M.
- Date : 03/09/1996
- Langues : Anglais
- Source : Applications for Natural Refrigerants
- Formats : PDF
Voir la fiche
-
Forane 408A.
- Auteurs : Elf Atochem
- Date : 10/1996
- Langues : Anglais
- Source : Tech. Dig. - 4 p.; 4 fig.; 5 tabl.
Voir la fiche