Document IIF

Corrélations empiriques relatives au transfert de chaleur et aux pertes par frottement pour des échangeurs à tubes ailetés, avec ailettes ondulées.

Empirical correlations for heat transfer and flow friction characteristics of herringbone wavy fin-and-tube heat exchangers.

Auteurs : WANG C. C., HWANG Y. M., LIN Y. T.

Type d'article : Article, Article de la RIF

Résumé

This study presents an empirical correlation describing the airside performance of herringbone wavy fin pattern. A total of 61 samples containing approximately 570 data points are used in the regression analysis. The proposed heat transfer correlation can describe 91% of the test data within plus or minus 15%, with a mean deviation of 6.98% while the proposed friction correlation can describe 85% of the database within plus or minus 15% with a mean deviation of 8.82%.

Documents disponibles

Format PDF

Pages : 673-680

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Empirical correlations for heat transfer and flow friction characteristics of herringbone wavy fin-and-tube heat exchangers.
  • Identifiant de la fiche : 2003-0101
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 25 - n. 5
  • Date d'édition : 08/2002

Liens


Voir d'autres articles du même numéro (18)
Voir la source