Document IIF

Cycle à absorption rentable améliorant l'interface charge/refroidisseur à absorption à chauffage direct et à double effet.

Cost-effective absorber cycle improves DFA chiller/load interface.

Auteurs : MECKLER M.

Résumé

The paper describes an enhanced absorption cycle utilizing a vapor recompression absorber (VRA), which can either be retrofitted into an existing or constructed as part of a new direct-fired double-effect absorption (DFA) chiller. The VRA employs uniquely configured concentric heat and mass transfer surfaces and is powered by a relatively small electric motor blower. Since the heat of compression is recovered as latent heat of evaporation, the VRA unit operates essentially as an absorber/low pressure differential heat pump while increasing the volume of the refrigerant water and further concentrating the absorbent, thereby decreasing the supply temperature to 2.2 °C or lower. This permits a higher chiller temperature-differential than presently possible while maintaining approximately the same overall system COP.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Cost-effective absorber cycle improves DFA chiller/load interface.
  • Identifiant de la fiche : 2000-1348
  • Langues : Anglais
  • Source : 20th International Congress of Refrigeration: Refrigeration into the Third Millennium.
  • Date d'édition : 19/09/1999

Liens


Voir d'autres communications du même compte rendu (447)
Voir le compte rendu de la conférence