Document IIF

Refroidisseur à absorption à triple effet et à échelle expérimentale utilisant la solution eau-bromure de lithium comme fluide actif : conception et installation.

Design/setup of the experimental-scale triple-effect absorption chiller using the aqueous lithium bromide solution as a working fluid.

Auteurs : KIM J. S., LEE H., PANG H. S., et al.

Résumé

Too high temperature of the lithium bromide solution is known to be very bad for corrosion in generators and absorbers. In the paper, a new absorption cycle using an additional vapour compression unit in the basic triple-effect absorption chiller cycle was considered to overcome the inherent problem. The high generator temperature can be lowered by properly using the vapour compression unit and thus changing the operating condition of the generator. An experimental-scale absorption chiller was designed and constructed based on a computer simulation. A brief characteristic of the current stage operation was also included.

Documents disponibles

Format PDF

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Design/setup of the experimental-scale triple-effect absorption chiller using the aqueous lithium bromide solution as a working fluid.
  • Identifiant de la fiche : 2000-1345
  • Langues : Anglais
  • Date d'édition : 19/09/1999
  • Source : Source : Prepr. 20th int. Congr. Refrig., Sydney
    pap. 312; 6 p.; fig.; tabl.; 11 ref.