Document IIF

CYCLE DE POMPE A CHALEUR A COMPRESSION DE VAPEUR AVEC ECHANGE DE CHALEUR ENTRE DESORBEUR ET ABSORBEUR.

VAPOUR COMPRESSION HEAT PUMP CYCLE WITH DESORBER-ABSORBER HEAT EXCHANGE.

Auteurs : RADERMACHER R.

Résumé

L'AUTEUR PRESENTE UNE POMPE A CHALEUR A COMPRESSION AVEC CIRCUIT DE SOLUTION. DANS CE CYCLE, LES INTERVALLES DE TEMPERATURE TRANSITOIRES SONT CHOISIS ASSEZ GRANDS POUR QUE LA TEMPERATURE LA PLUS ELEVEE DU DESORBEUR (EVAPORATEUR) SOIT SUPERIEURE A LA TEMPERATURE LA PLUS BASSE DE L'ABSORBEUR (CONDENSEUR). PAR SUITE, UNE PARTIE DE L'ABSORBEUR FOURNIT DE LA CHALEUR AU DESORBEUR, CE QUI ENTRAINE UNE DIFFERENCE DE PRESSION EXTREMEMENT FAIBLE AU COMPRESSEUR, TOUT EN AUGMENTANT LE DEBIT-MASSE POUR UNE PUISSANCE FRIGORIFIQUE DONNEE. POUR LES APPLICATIONS AVEC GRANDS ECARTS DE TEMPERATURE TRANSITOIRE ET UNE ELEVATION IMPORTANTE DE LA TEMPERATURE, ILSE PRODUIT UNE AUGMENTATION DU COP TANDIS QUE LES TAUX DE COMPRESSION RESTENT A 2 ENVIRON.

Documents disponibles

Format PDF

Pages : vol. B-E

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : VAPOUR COMPRESSION HEAT PUMP CYCLE WITH DESORBER-ABSORBER HEAT EXCHANGE.
  • Identifiant de la fiche : 1988-2468
  • Langues : Anglais
  • Source : Development in refrigeration, refrigeration for development. Proceedings of the XVIIth international Congress of Refrigeration.
  • Date d'édition : 24/08/1987

Liens


Voir d'autres communications du même compte rendu (509)
Voir le compte rendu de la conférence