Document IIF

Cycle frigorifique mixte utilisant un système de refroidissement à éjection.

A combined-cycle refrigeration system using ejector-cooling cycle as the bottom cycle.

Auteurs : HUANG B. J., PETRENKO V. A., CHANG J. M., et al.

Type d'article : Article, Article de la RIF

Résumé

A combined-cycle refrigeration system (CCRS) that comprises a conventional refrigeration and air-conditioning system using mechanical compressor (RAC/MC) and an ejector-cooling cycle (EJC) is proposed and studied. The EJC is driven by the waste heat from the RAC/MC and acts as the bottom cycle of the RAC/MC. A system analysis shows that the COP of a CCRS is significantly higher than a single-stage refrigeration system. Improvement in COP can be as high as 18.4% for evaporating temperature of the RAC/MC at -5 °C. A prototype of the CCRS was built and tested in the study, which shows that the CCRS using the ejector-cooling cycle as the bottom cycle of the RAC/MC is viable. Further improvement in COP is possible since the prototype is not designed and operated at an optimal condition.

Documents disponibles

Format PDF

Pages : 391-399

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : A combined-cycle refrigeration system using ejector-cooling cycle as the bottom cycle.
  • Identifiant de la fiche : 2001-2696
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 24 - n. 5
  • Date d'édition : 08/2001

Liens


Voir d'autres articles du même numéro (6)
Voir la source