Système frigorifique à compression de vapeur à cycle de refroidissement à éjecteur intégré.

Hybrid vapor compression refrigeration system with an integrated ejector cooling cycle.

Auteurs : ZHU Y., JIANG P. X.

Type d'article : Article, Article de la RIF

Résumé

A refrigeration system was developed which combines a basic vapor compression refrigeration cycle with an ejector cooling cycle. The ejector cooling cycle is driven by the waste heat from the condenser in the vapor compression refrigeration cycle. The additional cooling capacity from the ejector cycle is directly input into the evaporator of the vapor compression refrigeration cycle. The governing equations are derived based on energy and mass conservation in each component including the compressor, ejector, generator, booster and heat exchangers. The system performance is first analyzed for the on-design conditions. The results show that the COP is improved by 9.1% for R22 system. The system is then compared with a basic refrigeration system for variations of five important variables. The system analysis shows that this refrigeration system can effectively improve the COP by the ejector cycle with the refrigerant which has high compressor discharge temperature.

Documents disponibles

Format PDF

Pages : 68-78

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Hybrid vapor compression refrigeration system with an integrated ejector cooling cycle.
  • Identifiant de la fiche : 30003208
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 35 - n. 1
  • Date d'édition : 01/2012