Détermination de la densité de stockage frigorifique de coulis d’hydrate au moyen de la méthode calorimétrique par mélange.

[In Chinese. / En chinois.]

Auteurs : ZHANG L., LI P., LI N., et al.

Type d'article : Article

Résumé

Cool-storage density is one of the most important parameters for evaluating the performance of refrigerant hydrate. A calorimetric device was set up and a mixing calorimetry method was established to measure the cool-storage density of hydrate slurry according to the law of energy conservation. The cool-storage densities of hydrate slurries formed from R141b/H2 O coarse mixture and R141b/H2 O micro-mulsion were measured within 4 -12°C. The results are 49.6 kj/kg and 99.1 kj/kg, which are about 1.5 times and 3 times of that of water, respectively. Volume of storage tank could be reduced significantly by utilizing refrigerant hydrate slurry instead of water.

Documents disponibles

Format PDF

Pages : 47-52

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : [In Chinese. / En chinois.]
  • Identifiant de la fiche : 30020640
  • Langues : Chinois
  • Source : Journal of Refrigeration - vol. 35 - n. 160
  • Date d'édition : 12/2014