Document IIF

Développement d’un modèle dynamique pour des systèmes de stockage de glace sur serpentin à fonte externe.

Development of a dynamic model for ice-on-coil external melt storage systems.

Numéro : pap. n. 1361

Auteurs : NONNEMAN J., VOS W. M. de, MONTEYNE H., et al.

Résumé

Ice storage systems are commonly used to balance the intermittency of renewable energy and decrease the peak load by switching to off-peak hours. An adequate model is necessary to predict the behaviour of these systems. However, there is a scarce in detailed models available used to describe the performance of an ice storage evaporator and its use in a refrigeration cycle. Most existing models approximate the working principles with a steady analysis, not considering the sub cooling of ice and thickness distribution along the length. The developed model in this article uses a discretisation in length and radial direction together with an adapted thermal resistance matrix method to limit the calculation time. It has a great variability of boundary conditions and the ability to implement different types of refrigerants. The simulation results are in good agreement with the data of the manufacturer. The model shows that switching from R404A to R449A reduces the total electricity consumption.

Documents disponibles

Format PDF

Pages : 8

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Development of a dynamic model for ice-on-coil external melt storage systems.
  • Identifiant de la fiche : 30026753
  • Langues : Anglais
  • Source : Proceedings of the 25th IIR International Congress of Refrigeration: Montréal , Canada, August 24-30, 2019.
  • Date d'édition : 24/08/2019
  • DOI : http://dx.doi.org/10.18462/iir.icr.2019.1361
  • Notes :

    Keynote


Liens


Voir d'autres communications du même compte rendu (632)
Voir le compte rendu de la conférence