Document IIF

Développement d’une nouvelle structure expérimentale pour la collecte de de données expérimentales haute fidélité pour des échangeurs de chaleur air-frigorigène.

Development of novel experimental infrastructure for collection of high-fidelity experimental data for refrigerant to air heat exchangers.

Auteurs : SALEEM S., SARFRAZ O., BRADSHAW C. R., BACH C. K.

Type d'article : Article de la RIF

Résumé

Fin-and-tube refrigerant-to-air heat exchangers are one of the most common styles of heat exchangers in residential and light-commercial HVAC&R applications. To optimize trade-off between unit efficiency and production costs for units that use them most manufacturers rely on predictive modeling tools. High-fidelity predictive modeling tools require equally high-fidelity experimental data to validate model predictions.
This paper presents the design and development of a custom-designed pumped refrigerant loop that can test fin-and-tube heat exchangers in three modes: (1) single-phase refrigerant, (2) evaporator, and (3) condenser mode. This pumped refrigerant loop will be combined with a small-scale wind tunnel installed in a psychrometric chamber facility to enable acquisition of high-fidelity data to validate recently developed segment-by-segment fin-and-tube heat exchanger numerical models (Sarfraz et al., 2019, 2020). The pumped refrigerant loop allows precise control of desired test conditions, flowrate to each heat exchanger circuit, and is sized to test heat exchangers up to a capacity of five tons.
A preliminary test plan and detailed uncertainty analysis is developed for the first heat exchanger coil to be tested in the setup. The uncertainty analysis suggests that the experiment will be capable of measuring overall coil capacity within ±2%. A formalized design of experiments is also presented which suggests 9 tests per coil is a sufficient number to minimize experimental effort. A preliminary experiment was performed in evaporator mode that shows that air and refrigerant side capacities agree within 5%, which is in accordance with the energy balance limit set by ASHRAE Standard 33.

Documents disponibles

Format PDF

Pages : 189-200

Disponible

  • Prix public

    20 €

  • Prix membre*

    Gratuit

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : Development of novel experimental infrastructure for collection of high-fidelity experimental data for refrigerant to air heat exchangers.
  • Identifiant de la fiche : 30027458
  • Langues : Anglais
  • Source : International Journal of Refrigeration - Revue Internationale du Froid - vol. 114
  • Date d'édition : 06/2020
  • DOI : http://dx.doi.org/10.1016/j.ijrefrig.2020.02.024

Liens


Voir d'autres articles du même numéro (20)
Voir la source