Données sur la conception thermodynamique et évaluation de la performance d'un système à eau/bromure de lithium/bromure d'iode/bromure de nitrate/chlorure de lithium d'un refroidisseur à absorption.

Thermodynamic design data and performance evaluation of the water-lithium bromide-lithium iodide-lithium nitrate-lithium chloride system for absorption chiller.

Auteurs : LEE H. R., KOO K. K., JEONG S.

Type d'article : Article

Résumé

Dühring (P-T-X) and enthalpy concentration (H-X-T) diagrams of the H2O+LiBr+LiNO3+LiI+LiCl system were constructed by using the experimental data sets. Thermodynamic design data for a double-effect series-flow absorption chiller were calculated at various operating conditions by a computer simulation. The proposed working fluid was found to be applicable to cycle operation of air-cooled absorption chiller with no crystallization problems at higher absorber temperature.

Détails

  • Titre original : Thermodynamic design data and performance evaluation of the water-lithium bromide-lithium iodide-lithium nitrate-lithium chloride system for absorption chiller.
  • Identifiant de la fiche : 2001-0777
  • Langues : Anglais
  • Source : Applied Thermal Engineering - vol. 20 - n. 8
  • Date d'édition : 06/2000

Liens


Voir d'autres articles du même numéro (3)
Voir la source