Thermodynamic design data and performance evaluation of the water-lithium bromide-lithium iodide-lithium nitrate-lithium chloride system for absorption chiller.

Author(s) : LEE H. R., KOO K. K., JEONG S.

Type of article: Article

Summary

Dühring (P-T-X) and enthalpy concentration (H-X-T) diagrams of the H2O+LiBr+LiNO3+LiI+LiCl system were constructed by using the experimental data sets. Thermodynamic design data for a double-effect series-flow absorption chiller were calculated at various operating conditions by a computer simulation. The proposed working fluid was found to be applicable to cycle operation of air-cooled absorption chiller with no crystallization problems at higher absorber temperature.

Details

  • Original title: Thermodynamic design data and performance evaluation of the water-lithium bromide-lithium iodide-lithium nitrate-lithium chloride system for absorption chiller.
  • Record ID : 2001-0777
  • Languages: English
  • Source: Applied Thermal Engineering - vol. 20 - n. 8
  • Publication date: 2000/06

Links


See other articles in this issue (3)
See the source