Ébullition de HFO1234ze(E) à l’intérieur d’un échangeur à plaques brasées.

HFO1234ze(E) boiling inside a brazed plate heat exchanger.

Numéro : pap. 2166

Auteurs : LONGO G. A., MANCIN S., RIGHETTI G., et al.

Résumé

This paper investigates the effects of heat flux, saturation temperature, and outlet conditions on HFO1234ze(E) boiling inside a Brazed Plate Heat Exchanger (BPHE). The heat transfer coefficients show great sensitivity to heat flux and outlet conditions and weak sensitivity to saturation temperature (pressure). The frictional pressure drop shows a linear dependence on the refrigerant kinetic energy per unit volume. The two-phase flow boiling heat transfer coefficients were compared with a new model for refrigerant boiling inside BPHE (Longo et al., 2015): the mean absolute percentage deviation between calculated and experimental data is 7.2%. The present data points were compared with those of HFC134a and HFO1234yf previously measured inside the same BPHE under the same operating conditions: HFO1234ze(E) exhibits heat transfer coefficients very similar to HFC134a and HFO1234yf
and frictional pressure drops slightly higher than HFC134a and HFO1234yf.

Documents disponibles

Format PDF

Pages : 10

Disponible

  • Prix public

    20 €

  • Prix membre*

    15 €

* meilleur tarif applicable selon le type d'adhésion (voir le détail des avantages des adhésions individuelles et collectives)

Détails

  • Titre original : HFO1234ze(E) boiling inside a brazed plate heat exchanger.
  • Identifiant de la fiche : 30018936
  • Langues : Anglais
  • Source : 2016 Purdue Conferences. 16th International Refrigeration and Air-Conditioning Conference at Purdue.
  • Date d'édition : 11/07/2016

Liens


Voir d'autres communications du même compte rendu (274)